Step 1 Remove the re cylinder.
Step 2 Fill the re cylinder with extinguishant.
NO TE
This document does not provide details about how to ll the re cylinder with
extinguishant. Perform this operation in a dedicated station.
Extinguishant Chemical: HFC-227ea.
Extinguishant weight: 26 kg (maximum: 27 kg).
Purity requirement: not less than 99.9%.
Fire cylinder pressure: 2.5 MPa at 20°C.
(veried by lling nitrogen)
Step 3 Install the
re cylinder.
----End