Table 4-2 Ground cable description
Cable Type Cross-
Sectional
Area
Outer
Diameter
Source
Ground cable Single-core
outdoor
copper cable
and M10,
M12 OT/DT
terminals
16–95 mm
2
10–32 mm Prepared by
the customer
The specications of the ground cable are subject to this table or calculated
according to IEC 60364-5-54.
Connect Ground Cables
Step 1 Connect the main ground bar of the control unit cabin.
● The ground cable of the main ground bar in the control unit cabin must be
connected.
● After connecting the ground cable of the main ground bar in the control unit
cabin, close the cabin door in time.
LUNA2000-2.0MWH Series Smart String ESS
User Manual 4 Installation