● Set the automatic calibration functions.
Parameter Description
Automatic SOC calibration – If this parameter is set to Enable,
automatic charge and discharge
calibration is allowed for battery
racks. During calibration, the cut-
o SOC settings will be
ineective and the response of
the charge and discharge power
may be impacted temporarily.
▪ On-grid scenario: Automatic
charge calibration is allowed
for battery racks.
▪ O-grid scenario: Automatic
discharge calibration is
allowed for battery racks.
– If this parameter is set to
Disable, automatic charge and
discharge calibration is not
allowed for battery racks.
Automatic SOH calibration Set this parameter to Disable.
● Set PCS insulation resistance detection.
Parameter
Description
Detection start time Set the start time of the PCS
insulation resistance detection. The
default value is 02:00.
If a dialog box You are advised to
change the insulation resistance
detection time to the optimal
time:
XX:XX
is displayed, you are
advised to click Conrm and set
Detection start time to the optimal
time.
Step 7 Connect to the Huawei NMS.
LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
User Manual 10 Commissioning the ESS (SmartLogger WebUI)
Issue 10 (2023-11-07) Copyright © Huawei Digital Power Technologies Co., Ltd. 152