Fire
● If a re occurs, power o the system if it is safe to do so.
● Extinguish the re with carbon dioxide, FM-200 or ABC dry powder re
extinguishers.
● Ask reghters to avoid contact with high-voltage components during re
ghting to prevent the risk of electric shock.
● Overheating may cause battery deformation, faults, and leakage of corrosive
electrolytes or toxic gases. Use respiratory protective equipment and keep a
safe distance from the batteries to prevent skin irritation and chemical burns.
Fire Alarm Horn/Strobe
When the alarm indicator on the equipment blinks or buzzes:
● Do not approach.
● Do not open the door.
● Stay away immediately.
● Cut o the power supply remotely only when your safety is guaranteed.
Gas Exhaust
● Onsite personal protection: Do not directly face the exhaust vents.
● Post-disaster product maintenance: Contact the Company's service engineers
for evaluation.
Extinguishant Release or Fire
● Suggestions for onsite O&M personnel:
a. When a re occurs, evacuate from the building or equipment area, press
the re alarm bell, and immediately call the re emergency service.
Notify the professional reghters and provide them with relevant
product information, including but not limited to battery pack types, ESS
capacity, and battery pack location and distribution.
b. Do not enter the aected building or equipment area under any
circumstances, and do not open the doors of the ESS. Isolate and monitor
the site. Keep irrelevant personnel away from the site.
c. After calling the re emergency service, remotely power o the system
(such as the Smart Transformer Station, Smart PCS, auxiliary power
supply devices, and combiner box power supply) while ensuring your own
safety.
d. After professional reghters arrive, provide relevant product
information, including but not limited to battery pack types, ESS capacity,
battery pack location and distribution, and user manuals.
e. After the re is extinguished, the site must be handled by professionals in
accordance with local laws and regulations. Do not open the doors of the
ESS without permission.
LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
User Manual C Emergency Handling
Issue 10 (2023-11-07) Copyright © Huawei Digital Power Technologies Co., Ltd. 173