(10) Installation position of the
rack mounted re
extinguishing system
(11) Embedded power subrack (12) CMU and installation
position of the SmartModule
(13) Power distribution area (14) Water sensor (15) Adjustable column
(16) I/O expansion board - -
Table 2-3 Component conguration (2)
No. Item Maximum
Quantity
Congured
for an ESS
Description
1 Light 2 Used for lighting inside the cabinet.
2 Black start
button
1 Triggers the ESS black start.
3 CO sensor 2 Checks the concentration of CO in
combustible gases.
4 Door status
sensor
2 Monitors the door opening and
closing status.
5 Battery pack 12 A battery pack is a combination of
batteries connected in series and
output through a pair of positive and
negative terminals. It contains a
battery management module. The
battery management module
consists of the battery management
unit (BMU), battery optimization
module, and module fan.
6 Smoke
detector
1 Photoelectric smoke detector, used
for smoke detection.
7 Exhaust
controller
1 Works with the CO sensor and
exhaust fan to control air exhaust.
8 Exhaust
module
1 Exhausts combustible gases from the
cabinet.
9 T/H sensor 1 Measures the real-time ambient
temperature and humidity in the
cabinet.
10 Rack
mounted re
extinguishing
system
1 Used for re alarm and automatic
re extinguishing control.
11 Embedded
power
subrack
1 Provides installation positions for
components.
LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
User Manual 2 Product Description