Step 7 Install the system subrack into the cabinet, as shown in Figure 7-16.
1. Slide the system subrack into the cabinet along guide rails.
2. Use M6 screws to x the system subrack in the cabinet.
3. Ensure that the system subrack is horizontally installed and tightly screwed.
Figure 7-16 Installing a system subrack
Step 8 Connect the cables that you removed to the system subrack, making reference to
the labels you attached earlier.
Step 9 When the Power indicator is steady on, check whether the status of each
component is normal.
If yes, the system subrack has been successfully installed.
If no, cables are incorrectly connected, components are incorrectly installed, or
the newly installed system subrack is faulty.
Step 10
Conrm the replacement.
1. Perform a post-replacement inspection.
After the parts replacement, return to the SmartKit page and click Replaced.
Then complete the parts check after the replacement as prompted.
If the 0xF00CE002A and 0xF00D00016 alarms are generated and contain the SN of the
faulty system subrack that has been replaced, check the device conguration
according to the alarm information. If the conguration is correct, log in to
DeviceManager to manually clear the alarms, return to the SmartKit page, and click
Recheck.
2. Check system status.
OceanStor V5 Series
Parts Replacement 7 Replacing FRUs
Issue 15 (2019-12-30) Copyright © Huawei Technologies Co., Ltd. 151