RMS-SNMP01A SNMP Card
User Manual
4 Managing the UPS on the WebUI
Copyright © Huawei Technologies Co., Ltd.
32
4.4.3 Param. Settings Page
In the UPS information area, choose Param. Settings > Alarm Settings, you can set the high
and low temperature and humidity alarm thresholds, as shown in Figure 4-12. If you click a
text box, the value range is displayed. Enter a value within the range. Table 4-3 lists the
default values and value ranges.
The Param. Settings is active only the SNMP card is equipped with a temperature and humidity sensor.
Figure 4-12 Parameter settings (alarm settings)
Table 4-3 Default parameter values and value ranges
Parameter
Default Value
Value Range
Overtemperature threshold
40°C
3060°C
Undertemperature threshold
C
30ºC to +10°C
Overhumidity threshold
90% RH
70100% RH
Underhumidity threshold
10% RH
040% RH
If a CIM is configured, in the UPS information area, choose Param. Settings > Battery
String Settings, and you can set the battery strings connected to each UPS, as shown in
Figure 4-13.
Number of battery strings: The information about the battery strings connected to the
UPS. A maximum of four battery strings can be added for each UPS.
Number of batteries in a battery string: The number of batteries in each battery string.
Batteries String No.: The No. of battery string connected to the UPS. The No. cannot be
greater than the number of battery strings set on this page.