RMS-SNMP01A SNMP Card
User Manual
4 Managing the UPS on the WebUI
Copyright © Huawei Technologies Co., Ltd.
If you use Huawei NetEco, set Trap port to 162.
4.6.6 RCCMD
The UPS2000 SNMP card integrates the functions of the Generex RCCMD server:
When the UPS generates an alarm, the SNMP card sends a shutdown command
notification message, execution command, or trap message to the RCCMD client.
The SNMP card configures and saves the address and port for receiving the shutdown
command, and the message sending mechanism.
For a parallel system, select the ESN of the UPS into which the SNMP card is inserted every
time the SNMP card is powered on. Ensure that the entered ESN is consistent with the ESN of
the UPS into which the SNMP card is inserted. Otherwise, the client cannot receive the
correct shutdown command or event message. For the ESN of the UPS, see the manual
delivered with the UPS.
ESN Configuration
If a single UPS is online, the ESN of the UPS is displayed by default. The ESN cannot be set,
as shown in Figure 4-38. If the SNMP card is inserted into a parallel system, the ESN is
empty during first login. Select the ESN of the UPS where the SNMP card is inserted. If the
system experiences a power failure and restarts, the value set last time is displayed by default.
If the UPS system where the SNMP card is inserted is changed, and the ESN set previously does not
exist in the new system, the ESN is empty by default.
Figure 4-38 ESN configuration
RCCMD
RCCMD shutdown is Disabled by default, as shown in Figure 4-39. If required, set it to
Enabled upon first login. After you submit successfully, the page refreshes. The controls such
as SSL Encrypted Transmission and Client Configuration will be displayed on the page, as
shown in Figure 4-40.