RMS-SNMP01A SNMP Card
User Manual
9 Protecting the Server by Using the RCCMD Software
Copyright © Huawei Technologies Co., Ltd.
66
9 Protecting the Server by Using the
RCCMD Software
9.1 Introduction to the Software
The RCCMD shutdown software is part of the centralized monitoring system of the Generex
network. The UPS2000 SNMP card integrates the functions of the Generex RCCMD server:
Sends a shutdown command, notification message, execution command, or trap message
to the RCCMD client.
Receives the message "UPS alive check" sent by the RCCMD client and replies with the
system status.
Configures and saves the address and port for receiving the shutdown command, and the
message sending mechanism.
For the method of installing the RCCMD client, see the manual related to the RCCMD.
9.2 RCCMD Event Shutdown and Message Sending
Procedure
Step 1 On the RCCMD client, choose Connections, add the SNMP card IP address, and set the
encryption mode to encryption, as shown in Figure 9-1.
If encryption is disabled, you do not need to select the encrypted transmission.
All configurations take effect only after restart.