EasyManua.ls Logo

Huawei UPS2000-G Series - Page 107

Huawei UPS2000-G Series
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NO TE
Complete the quick settings based on the actual situation. If the quick settings are not
complete, the quick settings dialog box will be displayed in subsequent startup.
Non-initial startup
When the initialization is complete, the standby screen is displayed. On the
standby screen, press
to enter the main menu. Choose Main Menu >
Settings > System Parameters > Output to view output settings: if the
system uses three-phase input three-phase output, set Output mode to
Three-phase; if the system uses three-phase input single-phase output or
single-phase input single-phase output, set Output mode to Single-phase.
Set Voltage level and Frequency level based on the rated voltage and
frequency. Press ESC to return to the standby screen.
Figure 5-2 Non-initial startup
Step 5 Start the UPS in normal mode by using one of the following methods:
On the standby screen, hold down more than 5 seconds. Release the
button when you hear a beep sound. The startup screen is displayed. If the
UPS starts successfully, it enters normal mode.
UPS2000-G-(6 kVA-20 kVA)
User Manual 5 Operations
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 99

Table of Contents

Other manuals for Huawei UPS2000-G Series

Related product manuals