Battery Maintenance Precautions
Before battery maintenance, insulate tools such as wrenches. Do not place
any objects on the top of batteries.
Do not use any organic solvent to clean batteries.
Do not remove the safety valve or ll anything into a battery.
Do not smoke or use an open
ame around batteries.
After battery discharge, charge the battery in time to maintain a good service
life.
Only professionals are allowed to perform the maintenance tasks.
If batteries have not been discharged for a long time, discharge and charge
them in equalized mode at least once every three months to activate them.
Each charge should last at least four hours.
Normally, discharge and charge batteries once every four to six months. Each
charge should last at least four hours.
In high-temperature areas, discharge and charge batteries once every two
months. Each charge should last at least four hours.
Do not overdischarge batteries. After discharging batteries, fully charge them
immediately (within 24 hours) to avoid
aecting the battery capacity.
The maximum battery discharge duration can be set to 0 hours to 24 hours.
The default value is 16Hour. If you set the value to 0Hour, the discharge
duration is not limited.
Battery Routine Maintenance
Table 7-2 Battery routine maintenance
Check
Item
Expected
Result
Troubleshooting Maintenance Interval
Battery
managem
ent alarm
No battery
management
alarm is
generated.
Find the alarm cause
based on the alarm
information.
Monthly
UPS2000-G-(6 kVA-20 kVA)
User Manual 7 Routine Maintenance
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 115

Table of Contents

Other manuals for Huawei UPS2000-G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G Series and is the answer not in the manual?

Huawei UPS2000-G Series Specifications

General IconGeneral
Frequency50/60 Hz
Output Power Factor0.9
Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
Capacity1 kVA, 2 kVA, 3 kVA
Input Voltage220 Vac (120 Vac/208 Vac/230 Vac/240 Vac)
Output Voltage220/230/240 VAC
EfficiencyUp to 95%
TopologyDouble conversion online
Battery TypeSealed Lead Acid
Communication PortsUSB, RS232
Optional CommunicationSNMP
Operating Temperature0°C to 40°C

Related product manuals