Check
Item
Expected
Result
Troubleshooting Maintenance Interval
Battery
appearanc
e
1. The surface is
clean and
tidy without
stains.
2. The battery
terminals are
intact.
3. Batteries are
free from
damage and
cracks.
4. Batteries are
free from
acid leakage.
5. Batteries are
not deformed
or bulged.
If an exception occurs,
contact technical
support.
Monthly
Battery
operating
temperatu
re
1. The battery
ambient
temperature
is 25±5°C.
2. The battery
operating
temperature
ranges from
0°C to 40°C.
3. Battery
charge and
discharge
conditions
meet the
requirements
specied in
the battery
specications
.
1. Identify the cause
of an abnormal
battery operating
temperature.
2. If the fault persists,
contact technical
support.
Monthly
UPS2000-G-(6 kVA-20 kVA)
User Manual 7 Routine Maintenance
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 116