Huawei UPS2000-G Series - Maintain Batteries; About

Huawei UPS2000-G Series
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range Preset Value
Commun
ication
Card
IP address
(SNMP Card)
- 1.0.0.0–
253.255.255.255
192.168.0.10
Subn. mask
(SNMP Card)
- 0.0.0.0–
255.255.255.255
255.255.255.0
Gateway
(SNMP Card)
- 1.0.0.0–
253.255.255.255
192.168.0.1
Communicati
on address
(Modbus
Card)
- - -
Baud rate
(Modbus
Card)
- - -
Normal
mode (Dry
contact)
- Dry contacts 1–6 Dry contact 1
Battery mode
(Dry contact)
- Dry contacts 1–6 Dry contact 2
Bypass mode
(Dry contact)
- Dry contacts 1–6 Dry contact 3
Batt.
undervolt
(Dry contact)
- Dry contacts 1–6 Dry contact 4
BPS backfeed
(Dry contact)
- Dry contacts 1–6 Dry contact 5
Faulty UPS
(Dry contact)
- Dry contacts 1–6 Dry contact 6
System
Paramete
rs
Parallel
(congurable
after the
inverter shuts
down)
Single/Parallel Single and
Parallel
Single
Redundant UPSs 0–3 0
Output
(congurable
after the
inverter shuts
down)
Output mode
(congurable
only on the
UPS2000-G-15
kVA/20 kVA)
Single-phase/
Three-phase
Three-phase (on
the UPS2000-
G-15 kVA/20 kVA)
UPS2000-G-(6 kVA-20 kVA)
User Manual D LCD Menus and Parameters
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 144