Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range Preset Value
Voltage level ● 208 V, 220 V,
230 V, and 240
V (on the
UPS2000-G-6
kVA/10 kVA)
● 208 V, 220 V,
230 V, and 240
V, single-phase
(on the
UPS2000-G-15
kVA/20 kVA)
● 380 V, 400 V,
and 415 V,
three-phase
(on the
UPS2000-G-15
kVA/20 kVA)
● 220 V (on the
UPS2000-G-6
kVA/10 kVA)
● 220 V, single-
phase (on the
UPS2000-G-15
kVA/20 kVA)
● 380 V, three-
phase (on the
UPS2000-G-15
kVA/20 kVA)
Frequency level 50 Hz, 60 Hz, and
Automatic
50 Hz
Converter mode Enabled and
Disabled
Disabled
Output
(congurable
in any mode)
Volt. adj. coef. ±5%, ±4%, ±3%,
±2%, ±1%,0%
0%
Bypass
(congurable
after the
inverter shuts
down)
Max. voltage 10%, 15%, 20%,
25%, and 30%
15%
Min. voltage 10%, 20%, 30%,
40%, 50%, and
60%
20%
Frequency range ±0.5 Hz, ±1 Hz,
±2 Hz, ±3 Hz, ±4
Hz, ±5 Hz, and ±6
Hz
±2 Hz
ECO
(congurable
after the
inverter shuts
down)
Max. voltage 5%, 6%, 7%, 8%,
9%, and 10%
10%
Min. voltage 5%, 6%, 7%, 8%,
9%, and 10%
10%
Frequency range ±0.5 Hz, ±1 Hz,
±2 Hz, and ±3 Hz
±2 Hz
Single UPS ECO Enabled and
Disabled
Disabled
UPS2000-G-(6 kVA-20 kVA)
User Manual D LCD Menus and Parameters
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 145