Huawei UPS2000-G Series - Cleaning or Replacing the Air Filter (6 kVA and 10 kVA); Prerequisites; Procedure

Huawei UPS2000-G Series
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range Preset Value
Power
segment
Dis. time thres.
(congurable in
non-battery
mode)
0–999 minutes 30 min
Dis. volt. thres.
(congurable in
non-battery
mode)
1.90–2.25 V/cell 2.00 V/cell
Power Segment
(congurable
after the
inverter shuts
down)
Enabled and
Disabled
Disabled
Self-Load Output power
ratio
20%–100% 80%
Self-load mode Enabled and
Disabled
Disabled
Others
(congurable
after the
inverter shuts
down)
Recovery delay
time
0–900s 5S
Max. BPS
transfers
1–3 3
Output
transformer
Enabled and
Disabled
Disabled
Generator mode Weak adaptability
mode, Balanced
mode, and Strong
adaptability mode
Balanced mode
Auto check
capa.
(congurable
only for the
UPS2000-G-15
kVA/20 kVA)
Enabled and
Disabled
Enabled
Auto start Enabled and
Disabled
Disabled
No battery
alarm
(congurable
only when
batteries are not
connected)
Enabled and
Disabled
Enabled
UPS2000-G-(6 kVA-20 kVA)
User Manual D LCD Menus and Parameters
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 146