No. Item Expected Result
10 Battery voltage range 6 kVA/10 kVA: Use a multimeter to
measure the voltage between the
positive and negative battery
terminals. Voltage range: 9.6 V x
Number of batteries to 14.4 V x
Number of batteries. For example,
if 20 batteries are installed, the
voltage between the positive and
negative battery terminals should
range from 192 V (20 x 9.6 V) to
288 V (20 x 14.4 V).
15 kVA/20 kVA: Use a multimeter
to measure the voltages of the
positive and negative battery
strings. Voltage range: 9.6 V x
Number of batteries to 14.4 V x
Number of batteries. For example,
if both the positive and negative
battery strings contain 20 batteries,
the voltage of each battery string
should range from 192 V (20 x 9.6
V) to 288 V (20 x 14.4 V).