Table 4-25 Basic screen (UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01)
Item Description Default Value Value Range
Positive
batteries
and
Negative
batteries
Set the number of batteries.
When the number of
batteries N is less than 20,
the system output power is
derated to N/20 in battery
mode. The parameter is
congurable in non-battery
mode or non-battery ECO
mode.
0 16–20
Battery
capacity
Set the battery string
capacity. This parameter
indicates the sum of all
battery capacities. Set the
parameters based on the
actual battery capacity. The
parameter is
congurable
in non-battery mode or
non-battery ECO mode.
65 Ah 7–1000 Ah
Intelli.
Hibernati
on
When it is set to Enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Overtemp
. thres.
Set an alarm threshold for
high battery temperatures.
The parameter is
congurable in any mode.
50°C 45–55°C
Undertem
p. thres.
Set an alarm threshold for
low battery temperatures.
The parameter is
congurable in any mode.
–5°C –30°C to +5°C
Charge
curr. limit
Set a charge current limit.
The parameter is
congurable in any mode.
2.0 A 1.0–4.0 A
Overcurre
nt thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable
in any mode.
6.0 A 4.0–8.0 A
Battery
string
sharing
Specify whether battery
string sharing is supported
in a parallel system.
Disabled Disabled,
Enabled
UPS2000-G-(6 kVA-20 kVA)