Table 4-25 Basic screen (UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01)
Item Description Default Value Value Range
Positive
batteries
and
Negative
batteries
Set the number of batteries.
When the number of
batteries N is less than 20,
the system output power is
derated to N/20 in battery
mode. The parameter is
congurable in non-battery
mode or non-battery ECO
mode.
0 16–20
Battery
capacity
Set the battery string
capacity. This parameter
indicates the sum of all
battery capacities. Set the
parameters based on the
actual battery capacity. The
parameter is
congurable
in non-battery mode or
non-battery ECO mode.
65 Ah 7–1000 Ah
Intelli.
Hibernati
on
When it is set to Enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Overtemp
. thres.
Set an alarm threshold for
high battery temperatures.
The parameter is
congurable in any mode.
50°C 45–55°C
Undertem
p. thres.
Set an alarm threshold for
low battery temperatures.
The parameter is
congurable in any mode.
–5°C –30°C to +5°C
Charge
curr. limit
Set a charge current limit.
The parameter is
congurable in any mode.
2.0 A 1.0–4.0 A
Overcurre
nt thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable
in any mode.
6.0 A 4.0–8.0 A
Battery
string
sharing
Specify whether battery
string sharing is supported
in a parallel system.
Disabled Disabled,
Enabled
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 80