The battery sharing setting is available only for the UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01. Battery sharing is enabled for the UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL by default.
Figure 4-36 Basic screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-
G-15KRTL/UPS2000-G-20KRTL)
Table 4-26 Basic screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-
G-15KRTL/UPS2000-G-20KRTL)
Item Description Default Value Value Range
Positive
batteries
and
Negative
batteries
Set the number of batteries.
When the number of
batteries N is less than 20,
the system output power is
derated to N/20 in battery
mode. The parameter is
congurable in non-battery
mode or non-battery ECO
mode. You need to set the
number of batteries on the
UPS2000-G-6 kVA/10 kVA,
and set two battery strings
(positive and negative) on
the UPS2000-G-15 kVA/20
kVA.
0 16–20
Battery
capacity
Set the battery string
capacity. This parameter
indicates the sum of all
battery capacities. Set the
parameters based on the
actual battery capacity. The
parameter is
congurable in
non-battery mode or non-
battery ECO mode.
6 kVA standard
model: 7 Ah
6 kVA long
backup time
model: 40 Ah
10 kVA
standard
model: 9 Ah
10 kVA long
backup time
model: 65 Ah
15 kVA/20 kVA
long backup
time model: 65
Ah
7–1000 Ah
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 81