Item Description Default Value Value Range
Intelli.
Hibernati
on
When it is set to Enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Overtemp
. thres.
Set an alarm threshold for
high battery temperatures.
The parameter is
congurable in any mode.
50°C 45–55°C
Undertem
p. thres.
Set an alarm threshold for
low battery temperatures.
The parameter is
congurable in any mode.
–5°C –30°C to +5°C
Overcurre
nt thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable in
any mode.
Note: The overcurrent alarm
threshold can be set only
for the UPS2000-G-15
kVA/20 kVA.
Standard
model: 3.0 A
Long backup
time model:
6.0 A
Standard
model: 2.0–4.0
A
Long backup
time model:
4.0–8.0 A
Equalized Charge screen
Figure 4-37 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 4-27 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description Default
Value
Value Range
Equalized
charging
Determine whether to enable
equalized charging. The
parameter is congurable in
any mode.
Enabled Disabled,
Enabled
Time
interval
Set the interval for equalized
charging. The parameter is
congurable in any mode.
60 days 30–180 days
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 82

Table of Contents

Other manuals for Huawei UPS2000-G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G Series and is the answer not in the manual?

Huawei UPS2000-G Series Specifications

General IconGeneral
Frequency50/60 Hz
Output Power Factor0.9
Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
Capacity1 kVA, 2 kVA, 3 kVA
Input Voltage220 Vac (120 Vac/208 Vac/230 Vac/240 Vac)
Output Voltage220/230/240 VAC
EfficiencyUp to 95%
TopologyDouble conversion online
Battery TypeSealed Lead Acid
Communication PortsUSB, RS232
Optional CommunicationSNMP
Operating Temperature0°C to 40°C