Item Description Default Value Value Range
Intelli.
Hibernati
on
When it is set to Enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
congurable in any mode.
Disabled Disabled,
Enabled
Overtemp
. thres.
Set an alarm threshold for
high battery temperatures.
The parameter is
congurable in any mode.
50°C 45–55°C
Undertem
p. thres.
Set an alarm threshold for
low battery temperatures.
The parameter is
congurable in any mode.
–5°C –30°C to +5°C
Overcurre
nt thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable in
any mode.
Note: The overcurrent alarm
threshold can be set only
for the UPS2000-G-15
kVA/20 kVA.
Standard
model: 3.0 A
Long backup
time model:
6.0 A
Standard
model: 2.0–4.0
A
Long backup
time model:
4.0–8.0 A
● Equalized Charge screen
Figure 4-37 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 4-27 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description Default
Value
Value Range
Equalized
charging
Determine whether to enable
equalized charging. The
parameter is congurable in
any mode.
Enabled Disabled,
Enabled
Time
interval
Set the interval for equalized
charging. The parameter is
congurable in any mode.
60 days 30–180 days
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 82