Item Description Default
Value
Value Range
Voltage Set the battery equalized
voltage. The parameter is
congurable in any mode.
2.35 V/cell 2.33–2.40 V/cell
Max. time Set the maximum equalized
charge time. The parameter
is congurable in any mode.
960 min 600–999 min
Figure 4-38 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Table 4-28 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item
Description Default Value Value Range
Equalized
charging
Determine whether to
enable equalized charging.
The parameter is
congurable in any mode.
Enabled Disabled,
Enabled
Time
interval
Set the interval for
equalized charging. The
parameter is congurable in
any mode.
60 days 30–180 days
Voltage Set the battery equalized
voltage. The parameter is
congurable in any mode.
2.35 V/cell 2.33–2.40 V/
cell
Max.
current
Set the maximum equalized
current. The parameter is
congurable in any mode.
2.0 A Standard
model: 1.0–2.0
A
Long backup
time model:
1.0–4.0 A
Max. time Set the maximum equalized
charge time. The parameter
is congurable in any mode.
960 min 600–999 min
● Float Charge screen
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 83