UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
4 LCD and WebUI
Copyright © Huawei Technologies Co., Ltd.
126
Item
Description
Default Value
Value Range
EPO detection
Indicates whether to enable
emergency power-off (EPO).
EPO is performed only when this
parameter is enabled and the
EPO switch is triggered.
When EPO detection is changed
from Disable to Enable, check
that the EPO cable is connected
correctly.
Enable
Disable, Enable
D.G. ECO
bypass supply
Indicates whether ECO bypass is
allowed to supply power in D.G.
mode. When the D.G. is
connected to the dry contact
signal GEN:
If this parameter is set to
Enable, the system can enter
ECO bypass mode when the
D.G. supplies power to the
bypass and the ECO function
is enabled.
If this parameter is set to
Disable, the system is not
allowed to enter ECO mode
when the D.G. supplies power
to the bypass.
Enable
Disable, Enable
RAM
verification
Enable or disable the memory
check function. If this parameter
is set to Enable, the control chip
RAM working status is checked
regularly. If this parameter is set
to Disable, regular check is
disabled.
Disable
Disable, Enable
Collect
real-time site
waveform
If this parameter is set to Enable,
one waveform can be stored
manually.
Disable
Disable, Enable
BCB trips in
case of EOD
If this parameter is set to Enable,
the BCB will trip in case of
EOD.
Enable
Disable, Enable
Input Setting
Item
Description
Default Value
Value Range