UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
8 Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
0–1000 m
When the altitude is above 1000 m (maximum 4000 m), see
IEC62040-3 to check how the load power is derated.
At 25°C and atmospheric pressure:
100% load: 58 dB (30/40 kVA); 63 dB (80 kVA)
8.4 Safety Regulations and EMC
EN62040-1: 2013
IEC62040-1: 2013
YD/T1095-2010
EN62040-2
IEC62040-2
IEC61000-3-11
IEC61000-3-12
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
EN61000-4-6
IEC61000-4-8
8.5 Mains Input Electrical Specifications
Three-phase, four-wire, PE wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
80–280 V AC (phase voltage)
At 30–40°C: The UPS works at full load when the voltage is
187–280 V AC and is derated to 40% load when the voltage
is 187–80 V AC.
At 0–30°C: The UPS works at full load when the voltage is
176–280 V AC and is derated to 40% load when the voltage
is 176–80 V AC.