5.8 Transferring from Maintenance Bypass Mode to
Normal Mode
Prerequisites
Before you transfer the UPS from maintenance bypass mode to normal mode, ensure that the
bypass input and output are normal.
Procedure
Step 1 Turn off the maintenance bypass switch.
Turn off the maintenance bypass switch, as shown in Figure 5-18 and Figure 5-19. The Maint.
breaker closed alarm disappears on the LCD and WebUI. View the system running diagram
on the LCD or WebUI to check that the UPS has transferred to bypass mode.
Figure 5-18 Turning off the maintenance bypass switch on the UPS5000-A-30 kVA/40 kVA