UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
4 LCD and WebUI
Copyright © Huawei Technologies Co., Ltd.
125
If NA is displayed for load ratio, the value is invalid or outside the range.
Table 4-13 Monitoring page details
Numb
er
Area
Function
1
Running status
area
Displays the power flow and UPS running information.
2
Menu bar
Displays alarms and real-time data, sets parameters, and
provides control commands.
The Active Alarms page is displayed by default.
3
Information
area
Displays system monitoring information.
4.3.2.1 Parameter Settings
Figure 4-32 Parameter Settings
System Settings
Item
Description
Default Value
Value Range
High ambient
temperature
alarm threshold
C)
An alarm is generated when the
ambient temperature reaches or
exceeds the threshold specified
by this parameter.
55
4060
Low ambient
temperature
alarm threshold
C)
An alarm is generated when the
ambient temperature is lower
than the threshold specified by
this parameter.
10
20 to 0