UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
4 LCD and WebUI
Copyright © Huawei Technologies Co., Ltd.
131
Item
Description
Default Value
Value Range
Max. batt. dis.
time (h)
Set the maximum battery
discharge time. When the
discharge time reaches this value,
the UPS powers off. The battery
discharge time can be set only to
0 hours or a value only in the
range of 1648 hours. If the time
is set to 0 hours, battery
discharge protection is not
implemented.
24
048
EOD restart
If the mains is not functioning
normally, the UPS will transfer
to battery mode. When batteries
reach the EOD threshold, the
bypass is disabled, and EOD
restart is Enable, the UPS will
restart as soon as the mains
resumes.
If EOD restart is disabled, clear
the alarm manually or enable the
restart function for the UPS.
Enable
Disable, Enable
EOD restart
delay (min)
If EOD restart is set to Enable,
the UPS starts working after the
time set for EOD restart delay
when the input recovers from the
power failure upon EOD.
10
11440
Undertemp.
alarm thresh.
C)
Battery temperatures can be
monitored in a timely manner. If
a battery overtemperature alarm
is detected, the charging current
limit decreases to 0.03 CA.
Battery charging stops if a
battery overtemperature
protection alarm (when the
temperature reaches the high
temperature threshold plus 3°C)
is generated.
C
20°C to +5°C
Overtemp.
alarm thresh.
C)
50°C
35°C to 55°C
Single batt.
float chg.
voltage
deviation alarm
thres. (%)
Single batt. float chg. voltage
deviation alarm thres. (%) and
Single batt. dis. voltage
deviation alarm thres. (%) are
used to check whether the cells in
10
530