SitePlanning‐LocationConsiderations
14
5.2.5 AirIntakeand ExhaustClearance
5.2.5.1 SupplyClearance
Thechillersareequippedwithremovableintakeairfiltersononesideofthemachine.Caremustbetakento
ensurethatadequateclearanceisprovidedtoensurefreshairisabletoentertheintakeairfilters.Atleast3
feetofclearanceisrequiredbetweentheintakeairfilterandanyob
structions.Iftheintakeairfilterisfacinga
facilitywallatleast6feetofclearanceisrequired.
5.2.5.2 ExhaustClearance
Atleast8feetofverticalclearanceisrequiredfromthetopoftheexhaustfanstothebuildingceilingorany
otherobstructionsthatcouldimpedee
xhaustairflow.
CAUTION
Installingthechillerinabuildingcornershouldbeavoided.Placingthechillerinacorner
preventsproperdissipationofthehotexhaustairandcausestheexhaustairtorecirculate
intothechillerairintake. Thisleadstohighrefrigerationheadpressure,poorchiller
performance,andoverheatingtheexhaustfanmotors.
CAUTION
Thechillercondense rfansarenotdesignedforducting.Ductingcreatesexcessive
backpressureonthefansandcancausethefanmotorstooverheat.
Figure4:ChillerAirIntakeandDischarg eClearances
Hypertherm, Inc. Part Number: 810540