AppendixC(DefaultControllerSettings)
66
AlarmSettings
Table14:DefaultAlarmSettings
Category Parameter Values UOM
TemperatureAlarms
Deviation 10.0(5.6) °F(°C)
OtempInhibit 10
Min
UtempInhibit 10
Min
ProcessFlowAlarms
Setpoint 0.4(1.5) GPM(LPM)
InhibitTime 20 s
RecircFlowAlarms
Setpoint 6(22.7) GPM(LPM)
InhibitTime 20 s
ProcessFluidPressureAlarm
Setpoint 240(16.54) PSI(bar)
InhibitTime 3 s
TankLevelWarningsandFaults
Warning
OnAt 60.0 %
OffAt 80.0 %
Faults
OnAt 40.0 %
OffAt 60.0 %
LowRefrigerationPressure
Fault
OnAt 25.0(1.72) PSI(bar)
OffAt 50.0(3.45) PSI(bar)
InhibitTime 5 s
FilterChangeAlarm
MaxPercentIncrease 25.0(1.72) PSI(bar)
InhibitTime 20 Min
AmbientConditionWarnings
LowerLimit
OnAt 10.4(‐12.0)
°F(°C)
OffAt 14.0(‐10.0)
°F(°C)
UpperLimit
OnAt 125.6(52.0)
°F(°C)
OffAt 122.0(50.0)
°F(°C)
SystemLimits
TempLimitShutdown 115.0(46.1) °F(°C)
InhibitTime 10 Min
Enablebuzzer YES ‐‐‐
Hypertherm, Inc. Part Number: 810540