Maintenance‐ReplacingtheParticulateFilterCartridge
50
6. Scheduleplannedmaintenanceservices.
Consultthefactorytoscheduleandperformplannedmaintenanceservicesonthechillerbyqualified
refrigerationtechnicians.
10.2 ReplacingtheParticulateFilterCartridge
Thechiller’sprocesscircuitisequippedwithaparticulatefilter.Althoughthisprolongsthelifespanofthe
Chiller,thefiltercartridgewilleventuall ydeplete.Thechillermonitorswhenthecartridgeisnolonger
functionalandwilldisplayawarningonthecontroller.Ifthiswarningoccursthecartridgemustbereplaced
accordingtothefollowingsteps:
1. Shutth
echillerdownbyturningtheLocal/Off/RemoteSwitchbelowthecontrollertothe“O”position.
2. Accessthechiller’sairintake/filterside(refertosection6.4InternalAccess).
3. LocatetheparticulatefilterrefertoFigure41.
4. Carefullyunscrewthesumpofthefilterusingtheprovidedfilterwr
ench(typicallystoredintheinside
doorpocketoftheelectricalenclosurewhenshipped).Thesumpwillbefullofcoolantwhenremoved.
5. Removeanddiscardthedepletedfiltercartridgeandemptythesumpofcoolant.
6. Reinstallanewfiltercartridgeintothesump.
7. Reinstallth
esumpwiththenewfiltercartridgetakingcaretoensurethesumporingisproperlyseated.
8. Tightenthefiltersumpusingthefilterwrench.
9. Reinstalltheairintakefilter(s)beforerestartingchiller.
Hypertherm, Inc. Part Number: 810540

Table of Contents