EasyManua.ls Logo

Hypertherm Koolant Koolers N-Series - Mains Connectivity

Hypertherm Koolant Koolers N-Series
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation‐ElectricalSupplyMains
19
6.5.2 MainsConnectivity
Followtheprocedurebelowtoconnecttheappropriate3Phasepowertothechiller’smainci rcuitbreaker
disconnect.Thechillerisequippedwitha13/8”conduitfittingontherightsideoftheelectricalenclosure(See
Figure7)tofacilitatemainsconnectivity.
1. Opentheelectricalenclosurebyturningthemaincir
cuitbreakerdisconnecthandletotheOFFposition
andreleasingthequarterturnlatchesusingaflatheadscrewdriver(refer toFigure7).
2. Removethecapontheelectricalenclosureconduit(13/8”)locatedontherightsideofthechiller.
3. Routethesupplypowerthroughtheconduitandin
totheelectricalenclosure.
4. Wiremainspowertothemaincircuitbreakerdisconnectaccordingtothelabellocatedabovethe
disconnect.
5. Wirethegroundleadtotheprovidedgroundlu g(refertoFigure9).
WARNING
Thisprocedureinvolvesariskofelectricshockthatcouldcausepropertydamage,injury
and/ordeath.
Allelectricalconnectionsshouldbeperformedonlybyproperlytrainedandcertified
electricianswearingproperprotectivegearandusingproperlyinsulatedtools.
Beforeattemptingtomakeanyelectricalconnectionsordisconnectionstothechiller:
Verifythatthechille
r’smaincircuitbreakerdisconnecthandleisintheOFFposition
Verifythattheincomingpowertothechillerhasbeenturnedoff
Lockoutandtagoutthemainelectricalservicedisconnect
Useavoltmetertoverifythatthereisnoincomingpowertothechille
r
WARNING
Thelargestwiresizethatcanbesafelyacceptedbythemaincircuitbreakerdisconnectis6
AWG.Alwaysfollowallapplicableelectricalstandardsforselectingandinstallingwiresforthe
requiredpowerandcurrentratings.
CAUTION
Thechillerisequippedwithaphasemonitorthatpreventsincorrectphasewiringofincoming
mainpower.Ifthechiller’scontrollerdisplaysaphasemonitoralarm(alarmcodeAL*26)
swapanytwoofthethreeincomingmainpowerwiresthatconnecttothemaincircuit
breakerdisconnect.Donotswapanyoftheco
mpressors’,fan(s’)orpumps’wiringwithinthe
electricalenclosure.Allthechiller’scomponentshavebeenwiredcorrectandtestedatthe
factorypriortoshipping.Swappinganyofthechiller’scomponentswillleadtoincorrect
componentmotorrotation,damagetothechiller,andvoidthewarranty.
Hypertherm, Inc. Part Number: 810540

Table of Contents