Controller‐Monitoring
33
8.5 Monitoring
Thesescreensdisplayinformationregardingthechill er andprocess.
Figure13:Monitoring,Temperatures
Setpoint:Coolantsupplysetpointtemperature
(thisisadjustedinSETPOINTSunderthe
mainmenu).
Tout:Measuredcoolantsupplytemperature.
Tin:Measuredcoolantreturntemperature.
Figure14:Monitoring,SystemS tatus
HeatLoad:Calculatedprocessheatloadbased
onmeasuredflowrate,outlettemperature,
andinlettemperature.
CompCap:Coolingcapacityofthecompressors
atcurrentoperatingconditions.
DeltaTemp:DifferencebetweenInletand
OutletTemperature.
CoolDem:Percentageratioofcombinedcold
andCoolantheatloadstocoolingcap
acityof
compressoratcurrentoperatingconditions.
HotgasReq:Percentageofbypassedcooling
capacity.
Figure15:Monitoring,Condenser&SuctionData
CondPress:Measuredpressureofrefrigerant
atcondenseroutlet.
CondTemp:Measuredtemperatureof
refrigerantatcondenseroutlet.
Subcool:Calculatedsubcoolingvalueof
refrigerantatcondenseroutlet.
SuctPress:Measuredpressureofrefrigerant
atcompressorsuction.
SuctTemp:Measuredtemperatureof
refrigerantatcompressorsuct
ion.
Superheat:Calcula tedsuperheatvalueof
refrigerantatcompressorsuction.
Hypertherm, Inc. Part Number: 810540