Hypertherm Koolant Koolers N-Series - Alarm Settings

Hypertherm Koolant Koolers N-Series
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AppendixC(DefaultControllerSettings)
64
AppendixC(DefaultControllerSettings)
ProgramSettings
Table12:DefaultProgramSettings
Category Parameter Values UOM
CompressorSettings
OnDevn Setpoint+1.0(0.56)
°F(°C)
OffDevn Setpoint‐3.0(1.67)
°F(°C)
HeaterSettings
OnDevn Setpoint‐3.0(1.67)
°F(°C)
OffDevn Setpoint+0.0(0.0)
°F(°C)
PIDRegulationForFan
Deadband 2(0.14) PSI(bar)
Gain 10.0 ‐‐‐‐
IntegralTime 25.0 s
DerivativeTime 0 s
CondPressSetpoint 280.0(19.30) PSI(bar)
FanStartSettings
StartFan@100%for
AmbientTempOver
95.0(35.0) °F(°C)
KeepFan@100%For 2 Min
PIDRegulationfor
MotorizedHotGas
Deadband 0.1(.056) °F(°C)
Gain 10.0 ‐‐‐‐
IntegralTime 45 s
DerivativeTime 6 s
LOPSetpoint 55.0(3.79) PSI(bar)
PreposTime 20 S
EEVSettings(1/3)
SHSetpoint 15.0(8.3) °F(°C)
Gain 8.0 ‐‐‐‐
IntegralTime 30 s
DerivativeTime 0 s
EEVSettings(2/3)
LowSHThreshold 5.0(2.8) °F(°C)
SHIntegralTime 12.0 s
LOPThreshold 35.0(1.7) °F(°C)
LOPIntegralTime 12.0 s
EEVSettings(3/3)
MOPThreshold 23.0(12.8) °F(°C)
MOPIntegralTime 15.0 s
OpenonStart 100 %
PrePosTime 20 s
RecircPumpShutDown
TimeatStop
Time 10 s
PumpOutSettings
PumpOutTimeLimit 5 s
PumpOutPressLimit 35.0(2.4) PSI(bar)
TemperatureLimit
Setpoints
Min. 41.0(5.0)
°F(°C)
Max. 77.0(25.0)
°F(°C)
