EasyManua.ls Logo

Hypertherm Koolant Koolers N-Series - 9.2 Inline Heater Temperature Limit Switch; 9.3 Refrigeration High Pressure Switch

Hypertherm Koolant Koolers N-Series
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting‐AlarmList
46
Alarm
Code
AlarmName Type Description CorrectiveAction
AL*032 RecircFlowPrbErr
Auto
reset
Theflowsignalfromtheflow
meterintherecirculationcircuitis
readingopen,short,oroutof
range.
ChecktheM12Eurofastelectricalconnectoron
theflowmetertoensureitisfullytightened.
IfthefaultpersistscontactDTSService.
AL*033 RecircTempPrbErr
Auto
reset
Thetemperaturesignalfromthe
flowmeterintherecirculation
circuitisreadingopen,short,or
ourofrange.
ChecktheM12Eurofastelectricalconnectoron
theflowmetertoensureitisfullytightened.
IfthefaultpersistscontactDTSService.
AL*034 FlitInPressPrbErr
Auto
reset
Thepressuresignalfromfluidfilter
inletpressuretransduceris
readingopen,short,oroutof
range.
ChecktheM12Eurofastelectricalconnectoron
thepressuretransducertoensureitisfully
tightened.
IfthefaultpersistscontactDTSService.
AL*035
FiltOutPressPrb
Err
Auto
reset
Thepressuresignalfromfluidfilter
outletpressuretransduceris
readingopen,short,oroutof
range.
ChecktheM12Eurofastelectricalconnectoron
thepressuretransducertoensureitisfully
tightened.
IfthefaultpersistscontactDTSService.
AL*036
ProcessPressPrb
Err
Auto
reset
Thepressuresignalfromprocess
outletpressuretransduceris
readingopen,short,oroutof
range.
ChecktheM12Eurofastelectricalconnectoron
thepressuretransducertoensureitisfully
tightened.
IfthefaultpersistscontactDTSService.
AL*037
ProcessFlowMeter
Err
Auto
reset
Theflowsignalfromtheprocess
flowmeterisreadingopen,short,
oroutofrange.
ChecktheM12Eurofastelectricalconnectoron
theflowmetertoensureitisfullytightened.
IfthefaultpersistscontactDTSService.
AL*038 InletTempPrbErr
Auto
reset
Thetemperaturesignalfromthe
processflowmeterisreading
open,short,oroutofrange.
ChecktheM12Eurofastelectricalconnectoron
theflowmetertoensureitisfullytightened.
IfthefaultpersistscontactDTSService.
AL*039
TankLevelSensor
Err
Auto
reset
Thelevelsignalfromtheultrasonic
tanklevelsensorisreadingopen,
short,oroutofrange.
ChecktheM12Eurofastelectricalconnectoron
thetanklevelsensortoensureitisfully
tightened.
IfthefaultpersistscontactDTSService.
AL*040 CondTempPrbErr
Auto
reset
Thetemperaturesignalfromthe
condenserthermistorisreading
open,short,oroutofrange.
ChecktheDeutschelectricalconnectoronthe
thermistortoensureitisfullyinsertedintothe
matingconnectoronthewiringharness.
IfthefaultpersistscontactDTSService.
AL*041
SuctionTempPrb
Err
Auto
reset
Thetemperaturesignalfromthe
suctionthermistorisreadingopen,
short,oroutofrange.
ChecktheDeutschelectricalconnectoronthe
thermistortoensureitisfullyinsertedintothe
matingconnectoronthewiringharness.
IfthefaultpersistscontactDTSService.
AL*042 OutTempPrbErr
Auto
reset
Thetemperaturesignalfromthe
outletfluidthermistorisreading
open,short,oroutofrange.
ChecktheDeutschelectricalconnectoronthe
thermistortoensureitisfullyinsertedintothe
matingconnectoronthewiringharness.
IfthefaultpersistscontactDTSService.
AL*043 CondPressPrbErr
Auto
reset
Thepressuresignalfromthe
condenserpressuretransduceris
readingopen,short,oroutof
range.
Checktheelectricalconnectoronthepressure
transducertoensureitisfullyinsertedintothe
matingconnectoronthewiringharness.
IfthefaultpersistscontactDTSService.
AL*044 SucPressPrbErr
Auto
reset
Thepressuresignalfromthe
condenserpressuretransduceris
readingopen,short,oroutof
range.
Checktheelectricalconnectoronthepressure
transducertoensureitisfullyinsertedintothe
matingconnectoronthewiringharness.
IfthefaultpersistscontactDTSService.
AL*045
AmbientTempPrb
Err
Auto
reset
Thetemperaturesignalfromthe
ambientthermistorisreading
open,short,oroutofrange.
ContactDTSService.
Hypertherm, Inc. Part Number: 810540