EasyManua.ls Logo

ICT PRT-CTRL-DIN-IP - Trouble Inputs

ICT PRT-CTRL-DIN-IP
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Duplex Input Configuration
V+
V-Z4 V- Z3 Z2 V- Z1
N.C Tamper
1K
Input 1
N.C Input Contact
Input 2
N.C Input Contact
2K4
The following table indicates the position and resistor configuration corresponding to each input address:
Input Address Position Resistor
1 Z1 1K
2 Z1 2K4
3 Z2 1K
4 Z2 2K4
5 Z3 1K
6 Z3 2K4
7 Z4 1K
8 Z4 2K4
9 Z5 1K
10 Z5 2K4
11 Z6 1K
12 Z6 2K4
13 Z7 1K
14 Z7 2K4
15 Z8 1K
16 Z8 2K4
Enabling duplex inputs will not change the programming of any existing inputs. These must be reprogrammed or
rewired to match the new addressing scheme.
Trouble Inputs
Each controller can monitor up to 64 local trouble inputs.
Trouble inputs are used to monitor the status of the controller and in most cases are not physically connected to
an external input. These can then be used to report a message to a monitoring station, remote computer, keypad
or siren.
The following table details the trouble inputs that are configured in the controller and the trouble type and group
that they activate.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 28