Technical Specifications
The following specifications are important and vital to the correct operation of this product. Failure to adhere to
the specifications will result in any warranty or guarantee that was provided becoming null and void.
Ordering Information
Order Code PRT-CTRL-DIN PRT-CTRL-DIN-IP
Product Name
Protege GX DIN Rail Integrated System
Controller
Protege GX DIN Rail Integrated System
Controller (IP only)
Power Supply
Operating Voltage 11-14V DC
Operating Current 120mA (Typical)
DC Output (Auxiliary) 10.45-13.85V DC 0.7A (Typical) electronic shutdown at 1.1A
Bell DC Output (Continuous) 10.4-13.45V DC 8 ohm 30W Siren or 1.1A (Typical) Electronic Shutdown at 1.6A
Bell DC Output (Inrush) 1500mA
Total Combined Current* 3.4A (max)
Electronic Disconnection 9.0V DC
Communication
Ethernet 10/100Mbps ethernet communication link
RS-485
3 RS-485 communication interface ports - 1 for module communication, 2 for
reader communication
USB Type-A
Modem 2400bps modem communication -
Readers
Readers
2 reader ports that can be independently configured for either Wiegand (up to
1024 bits configurable) or RS-485, allowing connection of up to 4 readers
providing entry/exit control for two doors **
RS-485 reader port connections support configuration for OSDP protocol
Inputs
Inputs (System Inputs) 8 high security monitored inputs
Outputs
Outputs
4 (50mA max) open collector outputs for reader LED and beeper or general
functions
Relay Outputs 2 Form C relays - 7A N.O/N.C. at 30V AC/DC resistive/inductive
Dimensions
Dimensions (L x W x H) 156 x 90 x 60mm (6.14 x 3.54 x 2.36")
Net Weight 360g (12.7oz) 348g (12.3oz)
Gross Weight 440g (15.5oz) 428g (15.1oz)
Operating Conditions
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 43