UL Operation Mode
UL operation mode should be enabled in Protege GX system settings. Select Sites | Controllers | Options and
then select Advance UL Operation for the Protege GX system to operate in UL compliance mode.
This setting has the following effects:
Adds a 10 second grace period following a failed poll before a module is reported as offline.
Each module sends a poll message to the controller every 250 seconds. The module will be reported as offline
if no poll has been received for the duration of this poll time plus the 10 second grace period.
Suppresses reporting of all alarms and/or reportable events to a monitoring station within the first two
minutes of the controller powering up. The system will continue to send poll messages as usual.
Reports 'Input Tamper' events as 'Input Open' events when the area that the input is assigned to is armed. If
the area is disarmed an 'Input Tamper' message will be sent.
Limits the Dial attempts for reporting services to a maximum of 8.
This setting must be used in conjunction with the other configuration requirements as noted in this section.
ULC Compliance Requirements
CAN/ULC-S304
Auto Arming
Control units that support auto arming shall provide an audible signal throughout the protected area not less
than 10 min prior to the auto arming taking place. The control unit shall allow authorized users to cancel the
auto arming sequence and transmit such cancelation to the signal receiving center with the identification of
the authorized user that canceled the action.
The following options must be enabled in the Protege system when using the Auto Arming feature. When the
defer warning time is programmed to 10 minutes, the output group will be activated 10 minutes before the
system performs the Auto Arming in the associated Area.
- The Defer Output or Output Group must be programmed. Refer to the section Areas | Outputs in the
Operator Reference Manual for programming instructions.
- The Defer Warning Time must be programmed to not less than 10 minutes. Refer to the section Areas |
Configuration in the Operator Reference Manual.
- The Defer Automatic Arming option must be enabled. Refer to the section Areas | Options (2) in the
Operator Reference Manual.
Arming Signal
A bell or visual indicator used as an arming acknowledgment signal must be listed to a ULC security, signaling
or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Double EOL Input Configuration
Only double EOL Input Configuration shall be used. Refer to the Inputs section of this manual and the section
Inputs | Options in the Operator Reference Manual.
Multiplex System and Poll Time
The Protege controller is compatible with the ArmorIP Internet Monitoring Receiver. Poll Time must be set to
40 seconds and the Grace Time must be set to 20 seconds.
In the Protege system, the reporting service must be configured to 40 seconds. The following options are
required for the service selected as Report IP type:
- The Log Polling Message option must be enabled. Refer to the section Report IP | Options in the Operator
Reference Manual.
- The Poll Time must be programmed to 40 seconds. Refer to the Report IP | General section in the
Operator Reference Manual.