EasyManua.ls Logo

ICT PRT-CTRL-DIN-IP - Installation Requirements; Wiring

ICT PRT-CTRL-DIN-IP
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Requirements
This equipment is to be installed in accordance with:
The product installation instructions
UL 681 - Installation and Classification of Burglar and Holdup Systems
UL 827 - Central-Station Alarm Services
CAN/ULC-S301, Central and Monitoring Station Burglar Alarm Systems
CAN/ULC-S302, Installation and Classification of Burglar Alarm Systems for Financial and Commercial
Premises, Safes and Vaults
CAN/ULC-S561, Installation and Services for Fire Signal Receiving Centres and Systems
The National Electrical Code, ANSI/NFPA 70
The Canadian Electrical Code, Part I, CSA C22.1
AS/NZS 2201.1 Intruder Alarm Systems
The Local Authority Having Jurisdiction (AHJ)
Wiring
P
UL
ULC
For UL/ULCinstallations the following wiring specifications must be observed.
Earth Ground Wiring: Minimum 14AWG solid copper wire.
Input Wiring: Maximum distance of 300m (1000ft) from the connected module when using 22 AWG.
Aux Wiring: Minimum 22AWG, maximum 16AWG (depends on length and current consumption).
For wire/cable size, a maximum of 5% voltage drop at the terminals of the powered device has to be observed.
Ethernet Wiring: CAT5e / CAT6. Maximum length 100m (330 ft).
Module Network Wiring: Recommended Belden 9842 or equivalent.
24AWG twisted pair with characteristic impedance of 120ohm. Maximum length 900m (3000ft).
CAT5e / CAT6 also supported for data transmission when using ground in the same cable. Maximum length
100m (330 ft).
Do not use extra wires in the cable to power devices.
PRT-CTRL-DIN | Protege GX DIN Rail Integrated System Controller | Installation Manual 7

Table of Contents

Related product manuals