EasyManua.ls Logo

IFM O1D300 - 10.3.3 Configure OUT1; 10.3.4 Setting of the switch points for hysteresis function OUT1; 10.3.5 Setting of the switch points for window function OUT1

IFM O1D300
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
10.3.2 Setting the display
Change to [EF]�
Select [diS] and make settings�
2 settings can be selected:
[ON] = the measured value display is activated in the Run mode�
Update of the measured values every 600 ms�
[OFF] = The measured value display is deactivated in the Run mode�
Press one button to indicate the current measured value for 15 s�
The update of the measured value only refers to the display� It has no
effect on the outputs�
Confirm with [MODE/ENTER]�
The LEDs remain active even if the display is deactivated�
10.3.3 Configure OUT1
Select [OU1] and set the switching functions�
Switching functions:
[Hno] = hysteresis function / normally open
[Hnc] = hysteresis function / normally closed
[Fno] = window function / normally open
[Fnc] = window function / normally closed
Confirm with [MODE/ENTER]�
10.3.4 Setting of the switch points for hysteresis function OUT1
In [OU1] select the output function [Hno] or [Hnc]�
Confirm with [MODE/ENTER]�
Select [SP1] and set the set point�
Confirm with [MODE/ENTER]�
Select [rP1] and set the reset point�
Confirm with [MODE/ENTER]�
10.3.5 Setting of the switch points for window function OUT1
In [OU1] select the output function [Fno] or [Fnc]�
Confirm with [MODE/ENTER]�
Select [SP1] and set the upper limit value�
Confirm with [MODE/ENTER]�
Select [rP1] and set the lower limit value�
Confirm with [MODE/ENTER]�

Table of Contents

Related product manuals