EasyManua.ls Logo

IFM O1D300 - 10.3.6 Configure OUT2; 10.3.7 Setting of the switch points for hysteresis function OUT2; 10.3.8 Setting of the switch points for window function OUT2; 10.3.9 Scaling of the measuring range (analogue output)

IFM O1D300
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
UK
10.3.6 Configure OUT2
Select [OU2]�
Set switching functions or analogue signals:
[Hno] = hysteresis function / normally open
[Hnc] = hysteresis function / normally closed
[Fno] = window function / normally open
[Fnc] = window function / normally closed
[I] = current output analogue 4���20 mA
[U] = voltage output analogue 0���10 V
Confirm with [MODE/ENTER]�
10.3.7 Setting of the switch points for hysteresis function OUT2
In [OU2] select the output function [Hno] or [Hnc]�
Confirm with [MODE/ENTER]�
Select [SP2] and set the set point�
Confirm with [MODE/ENTER]�
Select [rP2] and set the reset point�
Confirm with [MODE/ENTER]�
10.3.8 Setting of the switch points for window function OUT2
In [OU2] select the output function [Fno] or [Fnc]�
Confirm with [MODE/ENTER]�
[Select SP2] and set the upper limit value�
Confirm with [MODE/ENTER]�
Select [rP2] and set the lower limit value�
Confirm with [MODE/ENTER]�
10.3.9 Scaling of the measuring range (analogue output)
In [OU2] select [I] or [U]�
Confirm with [MODE/ENTER]�
Select [ASP] and set the "Analogue start point"� With [ASP] you define
at which measured value the output signal is 4 mA / 0 V
Confirm with [MODE/ENTER]�
Select [AEP] and set the "Analogue end point"�
With [AEP] you define at which measured value the output signal is 20
mA / 10 V� [AEP] can also be selected so that it is below [ASP]� This
implements a falling edge�
Confirm with [MODE/ENTER]�
Minimum distance between [ASP] and [AEP]: 10.0 cm.
When the minimum distance is not reached, the error message "SIZE" is
displayed�

Table of Contents

Related product manuals