Switching status of the outputs
Output function Level (L) Output status
[Fno]
L < [SPx]
Closed
L > [rPx]
[SPx] < L < [rPx] Open
[Fnc]
L < [SPx]
Open
L > [rPx]
[SPx] < L < [rPx] Closed
Both window limit values ([SPx] and [rPx]) work with a switching hysteresis�
→ 4.1.1 Hysteresis function / example for output function [Hno]
4.2 Analogue function
An analogue signal, which is proportional to the distance, can be provided at out-
put 2 (OUT2) → 10.3.9 Scaling of the measuring range (analogue output)�
4.2.1 Current output
Factory setting Measuring range scaled
9795,5 (AEP) 0 MEWASP AEP0 (ASP)
MEW= final value of the measuring range
In the set measuring range the output signal is between 4 and 20 mA�
Faults are also displayed → 12 Troubleshooting�