Example Hno
1� For the output function [Hno] the output switches on when the set point [SPx]
is exceeded in case of a rising level�
2� If the level falls again, the output switches off as soon as the level is below the
reset point [rPx]� The reset point [rPx] is below the set point [SPx]�
1



2



[SPx] =
set point;
[rSPx] = reset point; HY = hysteresis
If the output function [Hnc] has been selected, set and reset point are exchanged�
The output switches off for rising level� If the level falls below [rPx] again, the
output switches on�
Switching status of the outputs
Output function Level (L) Output status
[Hno] L > [SPx] Closed
L < [rPx] Open
[Hnc] L > [SPx] Open
L < [rPx] Closed