Problem Solving Page 29 - 3
29
NOTE:
Dia
g
nostic text
in the left column, is shown
bolded
{
become alarms if active for 48 hours
}
#
Printed / Faxed / Displayed
Alarm / Warning Text:
Alarm Type:
System WARNING / Error Descriptions and
ALARM Descriptions
(actions to take)
25
DRY WELL SENSOR
TSP-MWS ground water Monitoring Well
BriteSensor is not submerged in water @ Channel
#N
(it cannot detect a product leak unless it's
submerged in ground water... the well may not be
deep enough or the sensor long enough... contact
service provider)
26
EXTERNAL INPUT SENSOR
External N input module has detected an input
signal
(follow policy procedure at your site).
27
HIGH BRINE SENSOR
TSP-HIS BriteSensor @ Channel #N detected a
High Brine level
(Call service provider [to confirm
leak] and call your local Regulatory agency. Shut
down pump & dispenser if a leak test has failed on
that tank and see procedures at your site.)
28
LIQUID DETECTED / LIQUID SENSOR
Standard Sensor @ Channel #N detected a liquid
(run a tank leak test [depending on the sensor
location] and call service provider to identify the
liquid and retest sensor)
29
LOW BRINE SENSOR
TSP-HIS BriteSensor @ Channel #N detected a
Low Brine level
(Call service provider [to confirm
leak] and call your local Regulatory agency. Shut
down pump & dispenser if a leak test has failed on
that tank and see procedures at your site.)
30
PRODUCT PRESENT /
PRODUCT DETECTED
SENSOR
TSP-DIS, -DDS, -DTS, -MWS BriteSensor @
Channel #N detected Product / leak
(Call service
provider [confirm leak] call the local Regulatory
agency. Shut down pump & dispenser for that
tank and see procedures at your site. [replace
sensor])
31
STANDARD ALARM /
STANDARD INPUT
SENSOR
A Standard Sensor (type TSP-EIS, -HLS, -ULS) @
Channel #N has detected liquid
(run a tank leak
test [depending on the sensor location] and call
service provider to identify the liquid and retest
sensor)
32
SUMP FULL SENSOR
TSP-DDS, -DTS BriteSensor @ Channel #N
liquid... Sump Full alarm
(see site policy about
pumping containment sump waste water)
33
VAPOR DETECTED / VAPOR SENSOR
TSP-DVS BriteSensor @ Channel #N detected
product Vapor in the vapor monitoring well
(Call
service provider [to analyze the leak], call your
local Regulatory agency, and see procedures at
your site.)
34
WATER DETECTED SENSOR
TSP-DIS*, -DDS, DTS, DVS* BriteSensor @
Channel #N detected Water, some sensors* may
not be able to detect product when water is
present
(see procedures at your site)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Incon task sentinel TS-508 and is the answer not in the manual?

Incon task sentinel TS-508 Specifications

General IconGeneral
BrandIncon
Modeltask sentinel TS-508
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals