Page 11- 2 Tank Sentinel Setup Programming Guide
SCALD (tank leak) Test Menu
N = Tanks 1 – 8
(only the NO. of TANKS
SCALD TESTS
programmed in the System menu will appear)
CONFIDNCE
SCALD CONFIDENCE
99.0% Keep the default 99.0% value
90.0%
95.0%
97.5% Press
ENTER
to accept this data.
PRECISION
SCALD TEST PRECISION
+0.2 Keep the default 0.2 gph monthly test value
Press
ENTER
to accept this data.
INTERVAL
SCALD INTERVAL
18 Keep the default value
(
18
)
Press
ENTER
to accept this data.
QUALIFY (minimum volume percent before starting a test)
SCALD VOLUME QUALIFY
+0
0.0 to 99.0%
Use keypad to input a percentage.
Press
ENTER
to accept this data.
Reference Local codes (and/or State / Province /
Federal codes) for the minimum percentage of
tank-volume-capacity before a leak test results
can, or will, be considered acceptable. Input the
minimum-acceptable volume based on these
regulations.
ENABLE (select tanks to be SCALD leak tested)
SCALD ENABLE
Keep the default – all tanks ENABLED
TANK 1
TANK 2 Use
UP/DOWN
▲
▼ keys to show more choices.
:
TANK 8 Press the (
M
) key to select a TANK #.
SCALD ENABLE
ENABLED
Use
UP/DOWN
▲
▼ keys to change the setting.
DISABLED Press
ENTER
to accept this data.
Press the
CANCEL
key to return to the SCALD TESTS menus.
— C
ONTINUED
ON
NEXT
PA GE
—
Monthly
Compliance
Yearly Test
SCALD Leak Test:
0.2 gph 0.1 gph
Precision:
Threshold = 1/2 of Leak Test value