Mechanical Installation (T10 to T12 Models)
94
Figure 5‑5 Top view of a cabinet for T11 and T12 models
To place the T11 or T12 model in a nine‑fold profile cabinet 600 mm in depth, fold
the back mounting plate inward, as shown in "
Figure 5–6
"
on page 94
, to borrow
the space of the column, which does not apply to the installation in a standard
cabinet greater than 800 mm in depth. A 600 mm deep cabinet with both front
access and back access is unable to house a T11 or T12 model. In this case, a
standard cabinet with a depth of 800 mm is recommended.
Figure 5‑6 Perspective view of a cabinet for T11 and T12 models
2. Fix the bottom mounting bracket in a nine‑fold profile cabinet.
Use six M5 self‑tapping screws to fix the mounting bracket onto the rack base of the
nine‑fold profile cabinet, as shown in "
Figure 5–7
"
on page 95
.
Drill holes for the mounting bracket and assemble the bracket on site if the cabinet is not a
nine‑fold profile one.