EasyManuals Logo

Inovance MD520 Series Commissioning Guide

Inovance MD520 Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
Commissioning and Trial Run
‑43‑
2.2.3 Parameter Initialization
Parame
ter
Code
Parame
ter
Name
De
fault
Value Range Description
FP‑01
Parame
ter
initiali
zation
0
0: No action
1: Restore parameters (excluding
motor parameters) to factory
settings
2: Clear records
4: Back up current user
parameters
501: Restore user parameters from
backup
503: Restore parameters
(including motor parameters) to
factory settings
This parameter is used to set the action upon parameter
initialization of the AC drive.
0: No operation
The AC drive does not perform any operation.
1: Restore parameters (excluding motor parameters) to
factory settings
Parameters of the AC drive are restored to factory
settings except motor parameters, frequency reference
decimal (F0‑22), fault records, cumulative running time
(F7‑09), cumulative power‑on time (F7‑13), cumulative
power consumption (F7‑14), and drive unit heatsink
temperature (F7‑07).
2: Clear records
The fault records, cumulative running time (F7‑09),
cumulative power‑on time (F7‑13), and cumulative power
consumption (F7‑14) are cleared.
4: Back up current user parameters
The current user‑set parameters are backed up.
501: Restore user parameters from backup
Parameters backed up by setting FP‑01 to 4 are restored.
503: Restore parameters (including motor parameters) to
factory settings
All AC drive parameters are restored to factory settings
except FP‑00, FP‑01, and the parameters in group FF.
2.2.4 Software Version Check
Parame
ter Code
Parameter Name
Value Range
Description
F7‑10
Performance software
version
0.00655.35
This parameter displays the
performance software version of the
AC drive.
F7‑11
Function software
version
0.00 to
655.35
This parameter displays the function
software version of the AC drive.
F7‑15
Temporary performance
software version
0.00655.35
This parameter displays the
temporary performance software
version of the AC drive.
F7‑16
Temporary function
software version
0.00655.35
This parameter displays the
temporary function software version
of the AC drive.

Table of Contents

Other manuals for Inovance MD520 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD520 Series and is the answer not in the manual?

Inovance MD520 Series Specifications

General IconGeneral
BrandInovance
ModelMD520 Series
CategoryDC Drives
LanguageEnglish

Related product manuals