Commissioning and Trial Run
48
Parame
ter
Code
Parameter
Name
Default Value Range Description
F0‑02 Operation
command
source
selection
0 0: Operating
panel
1: Terminal
2:
Communication
3: User‑defined
It is used to determine the input channel of the AC drive control
commands, such as run, stop, forward run, reverse run, and jog
operation.
0: Operating panel
Control commands are input using the keys on the operating panel.
This mode is suitable for initial commissioning.
1: Terminal
Control commands are input using the DI of the AC drive. The DI can
be assigned with different functions such as start/stop, forward/
reverse run, jog, two‑wire/three‑wire mode, and multi‑speed
operation. This mode is suitable for most applications.
2: Communication control
Control commands are input through remote communication. The
AC drive must be equipped with a communication card to
communicate with the host controller. This mode is suitable for
remote control or centralized control on multiple equipment.
3: User‑defined
The command source is defined by the user as needed for
expansion.

Table of Contents

Other manuals for Inovance MD520 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD520 Series and is the answer not in the manual?

Inovance MD520 Series Specifications

General IconGeneral
BrandInovance
ModelMD520 Series
CategoryDC Drives
LanguageEnglish

Related product manuals