EasyManuals Logo

Inovance MD520 Series Commissioning Guide

Inovance MD520 Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
Commissioning and Trial Run
58
Parame
ter
Code
Parameter
Name
Value Range Default Description
F1‑37 Auto‑tuning
mode
0: No operation
1: Static auto‑tuning on
partial parameters of
asynchronous motor
2: Dynamic auto‑tuning
of asynchronous motor
3: Static auto‑tuning on
all parameters of
asynchronous motor
4: Inertia auto‑tuning
5: Dead zone auto‑
tuning
11: With‑load auto‑
tuning of synchronous
motor (excluding back
EMF)
12: No‑load dynamic
auto‑tuning of
synchronous motor
13: With‑load rotary
auto‑tuning of
synchronous motor
(excluding zero point
angle)
14: Auto‑tuning on gain
difference between U‑
phase and V‑phase
15: MTPA of reluctance
motor
0
A9‑40 Torque point
4 of friction
curve
‑320.00 N·m to 320.00
N·m
0.00
N·m
A9‑41 Torque point
5 of friction
curve
‑320.00 N·m to 320.00
N·m
0.00
N·m
A9‑42 Torque point
6 of friction
curve
‑320.00 N·m to 320.00
N·m
0.00
N·m
A9‑43 Torque point
7 of friction
curve
‑320.00 N·m to 320.00
N·m
0.00
N·m

Table of Contents

Other manuals for Inovance MD520 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD520 Series and is the answer not in the manual?

Inovance MD520 Series Specifications

General IconGeneral
BrandInovance
ModelMD520 Series
CategoryDC Drives
LanguageEnglish