Commissioning and Trial Run
‑77‑
19: Clear data set by UP/DOWN key or by terminal functioning as UP/DOWN key
When the main frequency is set through the operating panel, activating the terminal
clears the frequency that is set by the increment or decrement key on the operating
panel or the terminal functioning as UP/DOWN keys and resumes the frequency
reference to the value specified by F0‑08.
20: Control command switchover terminal 1
When the command is set through the terminal (F0‑02 = 1) and the DI is active, you
can switch between the terminal control mode and operating panel control mode.
When the command is set through communication (F0‑02 = 2) and the DI is active,
you can switch between the communication control mode and operating panel
control mode.
21: Acceleration/Deceleration inhibited
The drive runs at the current operating frequency without being affected by external
input frequency except that a stop command is received.
22: PID pause
The PID is deactivated temporarily. The drive maintains the current output frequency
without PID adjustment of the frequency source.
23: Simple PLC state reset
The terminal is used to reset the drive to the initial state of the simple PLC.
24: Wobble frequency pause
In the wobble process, when the terminal is active, the wobble frequency function is
paused and the drive outputs with the center frequency.
25: Counter input
In the counting process, the counted pulse is input when the terminal is active.
26: Counter reset
In the counting process, the counter status is cleared when the terminal is active.
27: Length count input
In the fixed length process, the counted length is input when the terminal is active.
28: Length reset
In the fixed length process, the length is set to zero when the terminal is active.
29: Torque control inhibited
When the terminal is active, the drive switches from the torque control mode to the
speed control mode. When the terminal is inactive, the drive switches back to the
torque control mode.
30: Pulse input
When DI5 is used as the pulse input terminal, DI5 must be assigned with this function.
31: Reserved

Table of Contents

Other manuals for Inovance MD520 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD520 Series and is the answer not in the manual?

Inovance MD520 Series Specifications

General IconGeneral
BrandInovance
ModelMD520 Series
CategoryDC Drives
LanguageEnglish

Related product manuals