Commissioning and Trial Run
‑91‑
The terminal outputs an active signal when the running frequency exceeds the
frequency detection value and stops outputting the active signal when the running
frequency is lower than the result of the detection value minus the frequency
detection hysteresis (F8‑28 x F8‑29).
26: Frequency 1 reached
The terminal outputs an active signal when the running frequency of the AC drive is
within the frequency detection range specified by F8‑30 (Detection frequency 1).
Frequency detection range: F8‑30 – F8‑31 x F0‑10 to F8‑30 + F8‑31 x F0‑10, where F0‑
10 is the maximum frequency
27: Frequency 2 reached
The terminal outputs an active signal when the running frequency of the AC drive is
within the frequency detection range specified by F8‑32 (Detection frequency 2).
Frequency detection range: F8‑32 – F8‑33 x F0‑10 to F8‑32 + F8‑33 x F0‑10, where F0‑
10 is the maximum frequency
28: Current 1 reached
The terminal outputs an active signal when the output current of the AC drive is
within the current detection range specified by F8‑38 (Detection current 1). Current
detection range: F8‑38 – F8‑39 x F1‑03 to F8‑38 + F8‑39 x F1‑03, where F1‑03 is the
rated motor current
29: Current 2 reached
The terminal outputs an active signal when the output current of the AC drive is
within the current detection range specified by F8‑40 (Detection current 2). Current
detection range = F8‑40 ‑ F8‑41 x F1‑03 to F8‑40 + F8‑41 x F1‑03, where F1‑03 is the
rated motor current
30: Timing duration reached
If the timing function (F8‑42) is enabled, the terminal outputs an active signal when
the current running time of the AC drive reaches the set timing duration. The timing
duration is defined by F8‑43 and F8‑44.
31: AI1 input limit exceeded
If the value of AI1 input is larger than the value of F8‑46 (AI1 input protection upper
limit) or lower than the value of F8‑45 (AI1 input protection lower limit), the terminal
outputs an active signal.
32: Load loss
The terminal outputs an active signal when load loss occurs.
33: Reverse running
The terminal outputs an active signal when the AC drive is running reversely.
34: Zero current status