Chapter 4: Menu reference
100 CDC4 Door Controller Installation and Programming Manual
See Dual badgeon page 103 (the two-badge option can be configured
separately for IN readers and OUT readers). Also see the “Two badge unlock,
one badge relock” section on page 103.
Card to PIN time
Note: Card to PIN time can be set per door on the CDC4.
If card and PIN functionality is used, you can define the amount of time permitted
between a user badging their card and entering their entire PIN.
If the PIN is not completely entered before the time expires, then the user will
need to repeat the door opening function.
Enter the time in seconds.
See the “Card and PIN” section on page 102 (the card and PIN option can be
configured separately for IN readers and OUT readers).
Roller door up time
Reserved for future use.
Roller door down time
Reserved for future use.
Pre-lock time
Once the door open input (door input 1) has been deactivated, the door controller
waits for the pre-lock time to expire before locking the door. If the door open input
activates during the pre-lock time, the door is deemed open and the pre-lock
timer is cancelled. The shunt continues during the pre-lock time.
Door input 1 is programmed on the Hardware tab for the door.
Enter the time in seconds.
Post lock time
The post-lock time allows time for a lock to fully engage. After the post lock time
has expired, the door is deemed secure, and the shunt is cancelled. If the door
open input (Door input 1) activates during the post-lock time, the door is deemed
open and the post lock timer is cancelled. The shunt continues during the post-
lock time.
Door input 1 is programmed on the Hardware tabon page 97.
Enter the time in seconds.
Multi-badge time
Note: Multi badge time can be set per door on the CDC4 door controller.
If Two-badgeon page 102 is enabled for the door, then this field defines the
amount of time permitted between the first and second badges. If the time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Interlogix CDC4 and is the answer not in the manual?

Interlogix CDC4 Specifications

General IconGeneral
BrandInterlogix
ModelCDC4
CategoryController
LanguageEnglish

Related product manuals