Optidrive Eco User Guide Revision 2.01
36
www.microlectra.nl
Extended Parameters
10
P4-02
Auto-tune Enable
0
1
0
-
When set to 1, the drive immediately carries out a non-rotating auto-tune to measure the motor parameters for optimum
control and efficiency. Following completion of the auto-tune, the parameter automatically returns to 0.
P4-03
Vector Speed Controller Proportional Gain
0.1
400.0
50.0
%
Sets the proportional gain value for the speed controller. Higher values provide better output frequency regulation and
response. Too high a value can cause instability or even over current trips. For applications requiring best possible performance,
the value should be adjusted to suit the connected load by gradually increasing the value and monitoring the actual output
speed of the load until the required dynamic behaviour is achieved with little or no overshoot where the output speed exceeds
the setpoint.
In general, the factory set value will be suitable for most fan and pump applications, higher friction loads can tolerate higher
values of proportional gain, and high inertia, low friction loads may require the gain to be reduced.
P4-04
Vector Speed Controller Integral Time Constant
0.001
2.000
0.050
s
Sets the integral time for the speed controller. Smaller values provide a faster response in reaction to motor load changes, at the
risk of introducing instability. For best dynamic performance, the value should be adjusted to suit the connected load.
P4-05
Motor Power Factor Cos Ø
0.00
0.99
-
When operating in Vector Speed motor control mode, this parameter must be set to the motor nameplate power factor
P4-07
Maximum Motoring Current / Torque Limit
0.0
150.0
110.0
%-
This parameter defines the maximum current or torque limit used by the drive.
P4-12
Thermal Overload Value Retention
0
1
0
-
0 : Disabled.
1 : Enabled. All Optidrives feature electronic thermal overload protection for the connected motor, designed to protect the
motor against damage. An internal overload accumulator monitors the motor output current over time, and will trip the drive if
the usage exceeds the thermal limit. When P4-12 is disabled, removing the power supply from the drive and re-applying will
reset the value of the accumulator. When P4-12 is enabled, the value is retained during power off.
P4-13
Output Phase Sequence
0
1
0
-
0 : U, V, W
1 : U, W, V. Direction of motor rotation when operating in a forward direction will be reversed.
10.4. Parameter Group 5 Communication Parameters
Par
Parameter Name
Minimum
Maximum
Default
Units
P5-01
Drive Fieldbus Address / MAC ID
0
63
-
1
Sets the Fieldbus address for the Optidrive.
When using Modbus RTU, this parameter sets the Node Address. Refer to section 11.2 for further information.
When Using BACnet MS/TP, this parameter sets the MAC ID. Refer to section 11.3 for further information.
P5-03
Modbus RTU / BACnet Baud rate
9.6
115.2
115.2
kbps
Sets the baud rate when Modbus/BACnet communications are used
9.6kbps, 19.2kpbs, 38.4kpbs, 57.6kpbs, 115 kbps, 76.8kbps
P5-04
Modbus RTU / BACnet Data Format
-
-
-
Sets the expected Modbus or BACnet telegram data format as follows
: No Parity, 1 stop bit
: No parity, 2 stop bits
: Odd parity, 1 stop bit
: Even parity, 1 stop bit
P5-05
Communications Loss Timeout
0.0
5.0
1.0
seconds
Sets the watchdog time period for the communications channel. If a valid telegram is not received by the Optidrive within this
time period, the drive will assume a loss of communications has occurred and react as selected below (P5-07)
P5-06
Communications Loss Action
0
3
0
-
Controls the behaviour of the drive following a loss of communications as determined by the above parameter setting (P5-06).
0: Trip & Coast To Stop
1: Ramp to Stop Then Trip
2: Ramp to Stop Only (No Trip)
3: Run at Preset Speed 4
P5-07
Fieldbus Ramp Control
0
1
0
-
Selects whether the acceleration and deceleration ramps are control directly via the Fieldbus, or by internal drive parameters P1-
03 and P1-04.
0 : Disabled. Ramps are control from internal drive parameters
1 : Enabled. Ramps are controlled directly by the Fieldbus
P5-08
Fieldbus Module PDO4
0
7
1
-
When using an optional Fieldbus interface, this parameter configures the parameter source for the 4th process data word
transferred from the drive to the network master during cyclic communications:
0 : Output Torque Output power in kW to one decimal place, e.g. 500 = 50.0%
1 : Output Power Output power in kW to two decimal places, e.g. 400 = 4.00kW
2 : Digital Input Status Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc.
3 : Analog Input 2 Signal Level 0 to 1000 = 0 to 100.0%
4 : Drive Heat-sink Temperature 0 to 100 = 0 to 100°C
5 : User Register 1 Can be accessed by PLC program or group 9 parameters
4 : User Register 2 Can be accessed by PLC program or group 9 parameters
7 : P0-80 Value - P0-80 value can be selected by P6-28

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Invertek Drives Eco Optidrive Series and is the answer not in the manual?

Invertek Drives Eco Optidrive Series Specifications

General IconGeneral
BrandInvertek Drives
ModelEco Optidrive Series
CategoryDC Drives
LanguageEnglish

Related product manuals